prEN 1491
Building valves - Expansion valves - Tests and requirements
Draft Public enquiryProject stage codes
1. Prioritetinių darbo temų pažymėjimas ir ekspertų skyrimas
2. Projektas
3. Viešoji apklausa
From 2026-09-15
till 2026-11-22
4. Closure of enquiry
5. Submission to Formal Vote
Organisation
CEN Europos standartizacijos komitetasICS
91.140.60 - Water supply systemsTechnical Committee
TK 29 Water supplyForeignTC'S
CEN/TC 164Number of comments
0Comment start date
2026-09-15Scope
This document specifies dimensions, materials and performance requirements (including methods of test) for expansion valves, of nominal sizes from DN 15 to DN 50, having working pressures ) from 0,1 MPa (1 bar) to 1,0 MPa (10 bar). Expansion valves are intended for fitting to the cold potable water supply of storage water heaters, having a maximum distribution temperature of 95 °C, for all energy sources. Expansion valves do not control the temperature and alone do not constitute the protection required for storage water heaters. Expansion valves limit pressure, in the water heaters to what they are fitted, that is produced by thermal expansion of the water. NOTE The use of the device specified in this document does not override the need to use controls (e.g. thermostats and cut-outs) which act directly on the power sources of water heaters (for more information see Annex A).