prEN 1489
Building valves - Pressure safety valves - Tests and requirements
Draft Public enquiryProject stage codes
1. Prioritetinių darbo temų pažymėjimas ir ekspertų skyrimas
2. Projektas
3. Viešoji apklausa
From 2026-09-15
till 2026-11-22
4. Closure of enquiry
5. Submission to Formal Vote
Organisation
CEN Europos standartizacijos komitetasICS
91.140.60 - Water supply systemsTechnical Committee
TK 29 Water supplyForeignTC'S
CEN/TC 164Number of comments
0Comment start date
2026-09-15Scope
This document specifies dimensions, materials and performance requirements, including methods of test, for pressure safety valves, of nominal sizes from DN 15 to DN 40, having working pressures from 0,1 MPa (1 bar) to 1,0 MPa (10 bar). Pressure safety valves are intended for fitting to the potable water supply of storage water heaters, having a maximum storage temperature of 95 °C. Pressure safety valves limit the pressure in hot water heaters. Pressure safety valves do not control the temperature and alone do not constitute the protection required for storage water heaters. They are not intended to act as expansion valves under normal conditions. NOTE The use of the device specified in this document does not override the need to use controls (e.g. thermostats and cut-outs) which act directly on the power sources of water heaters (for more information see Annex A).