prEN 14453
Devices to prevent pollution by backflow of potable water - Pipe interrupter with permanent atmospheric vent DN 10 to DN 20 - Family D, type C
Draft New
Comment end date
2026-06-07
Export comments
Project stage codes
1. Prioritetinių darbo temų pažymėjimas ir ekspertų skyrimas
2. Projektas
3. Viešoji apklausa
From 2026-04-06
till 2026-06-07
4. Closure of enquiry
5. Submission to Formal Vote
Organisation
CEN Europos standartizacijos komitetasICS
23.060.50 - Check valvesTechnical Committee
TK 29 Water supplyForeignTC'S
CEN/TC 164Number of comments
0Comment start date
2026-04-06Scope
This document specifies the field of application, the dimensional, the physico-chemical properties and the properties of general hydraulic, mechanical and acoustic design of pipe interrupters with permanent atmospheric vent family D Type C, intended to prevent pollution of potable water by backflow, caused by backsiphoning only. It is applicable to pipe interrupters with permanent atmospheric vent in denominations DN 10 up to DN 20. It covers pipe interrupters with permanent atmospheric vent of PN 10 that are capable of working without modification or adjustment: - at any pressure, up to 1 MPa (10 bar); - with any pressure variation, up to 1 MPa (10 bar); - in permanent duty at a limited temperature of 65 °C and for maximum 1 h at 90 °C. It specifies also the test methods and requirements for verifying their characteristics, the marking and the presentation at delivery. Backflow protection devices integrated in flushing valves are similar to DC and are not covered under this document. The requirements are stated in EN 12541.