CENELEC Europos elektrotechnikos standartizacijos komitetas

ICS

29.120.50 - Fuses and other overcurrent protection devices

Technical Committee

TK 5 Electrical engineering

ForeignTC'S

CLC/TC 23E

Number of comments

0

Comment start date

2026-02-07

Scope

IEC 61008-1:2024, Clause 1 is applicable except for the first paragraph, which is replaced by the first paragraph below, and the last paragraph, which is replaced by the second paragraph below: This part of IEC 61008 applies to residual current operated circuit-breakers, without integral overcurrent protection, for household and similar uses (hereafter referred to as RCCBs), classified according to IEC 61008-1:2024, 4.1.1. RCCBs according to this document are intended for voltages not exceeding 440 V AC with frequencies of 50 Hz, 60 Hz or 50/60 Hz and currents not exceeding 125 A, intended principally for protection against shock hazard. This document applies in conjunction with IEC 61008-1:2024. It specifies requirements, tests and test sequences to verify compliance and is used for certification purposes.

Relations

Keitinys
prEN IEC 61008-2-1:2026/prAA:2026

Residual current operated circuit-breakers without integral overcurrent protection for household and similar uses (RCCBs) - Part 2-1: RCCBs according to classification 4.1.1