EN 81-58:2022
Safety rules for the construction and installation of lifts - Examination and tests - Part 58: Landing doors fire resistance test
Draft NewProject stage codes
1. Decision on WI Proposal
2. Projektas
3. Viešoji apklausa
From 2020-10-15
till 2020-12-19
4. Closure of enquiry
5. Submission to Formal Vote
6. Išleidimas (Paskelbimas Biuletenyje)
Organisation
CEN Europos standartizacijos komitetasICS
13.220.20 - Fire protectionTechnical Committee
TK 77 LiftsForeignTC'S
CEN/TC 10Number of comments
0Scope
This document specifies the fire resistance requirements for lift landing doors which are intended to provide a barrier to the spread of fire from the landing side and via the lift well in buildings during a defined period of time. The fire resistance requirements are expressed in terms of integrity (E), insulation (EI) and radiation (EW). It is applicable to lift landing doors installed in the lift well openings at landings and used as means of access to lift car. It also specifies the method of testing and classification of fire resistance of lift landing doors. The test method is only valid for furnaces where the door is mounted in a vertical position. The test method specifies the measurement of integrity and if required the measurement of radiation and thermal insulation. This document does not cover other technical requirements in addition to fire resistance requirements. This document refers to CO2 as means of tracing the propagation of fire. The document does not cover hazards due to emission of gases. This document is not applicable to lifts which are installed before the date of its publication.Relations